Sales & Support: Request A Quote
Home ProductsHeat Release Test

BS 476-6 Fire Tests on Building Materials and Structures for Fire Propagation

BS 476-6 Fire Tests on Building Materials and Structures for Fire Propagation

    • BS 476-6 Fire Tests on Building Materials and Structures for Fire Propagation
    • BS 476-6 Fire Tests on Building Materials and Structures for Fire Propagation
    • BS 476-6 Fire Tests on Building Materials and Structures for Fire Propagation
    • BS 476-6 Fire Tests on Building Materials and Structures for Fire Propagation
  • BS 476-6 Fire Tests on Building Materials and Structures for Fire Propagation

    Product Details:

    Place of Origin: CHINA
    Brand Name: AI
    Certification: ISO
    Model Number: FPT

    Payment & Shipping Terms:

    Minimum Order Quantity: 1 SET
    Price: negotiable
    Packaging Details: Plywood case
    Delivery Time: 60 days
    Payment Terms: Western Union, T/T, L/C
    Supply Ability: 20 sets per month
    Contact Now
    Detailed Product Description
    Test Standard: BS476-6 Gas Supplies: G112, As Specified In BS 4947
    Weight: 46KG Warranty: 1 Year
    Color: White Power Supply: 230 Volts Nominal 10 Amps
    Keyword: Fire Propagation Test

    Fire Tests on Building Materials and Structures for Fire Propagation

     

    INTRODUCTION

    BS 476 part 6 specifies a method of test, the result being expressed as a fire propagation index, that provides a comparative measure of the contribution to the growth of fire made by an essentially flat material, composite or assembly. It is primarily intended for the assessment of the performance of internal wall and ceiling linings.​

     

    FEATURE

    • Stainless steel support frame and Calcium silicate board combustion chamber.

    • Three kinds of sample holders for different thickness of the specimens are supplied with fire propagation index tester.

    • Low reflective black finished mild steel Chimney and Cowl assembly complete with thermocouple mounting points.

    • Compliant stainless steel gas burner.

    • Two K type mineral insulated thermocouples complete with ceramic insulators.

    • Two pencil type heaters with 1000w installed in combustion chamber.

    • Control gas instrumentation including electronic gas on/off valve, flow regulating valve, flow meter and manometer.

    • Intelligent single phase power controller with feedback loop for accurate control of electric heating elements

    • DAQ record automatically the mV output from the thermocouples of the flue gases throughout the duration of the test.

    • According to the test time, the fire propagation index tester can automatically adjust the output power.

     

    Data Acquisition system:

    • Prompted software interface

    • Data recording and display of cowl temperature against time

    • Data recording and display of ambient temperature against time

    • Display of power value in kW

    • Calibration routine

    • Calculation of output rise and calibration value

    Installation requirements

    Electrical

    230 volts Nominal 10 Amps

    Ambient Temperature

    10°C to 35°C

    Gas supplies

    The gas supply specified in the Standard is Standard test gas G112, as specified in BS 4947

    Flow

    Gas flow for burner adjustable from 0 to 5 nl/min

    Pressure

    1KPa

    Dimensions

    Apparatus: 400mm (W) x 600mm x (H) x 300mm (D)

    Control module: 400mm (W) x 500mm x (H) x 400mm (D)

    Weight

    46KG

    Applicable standards

    BS476-6

     

    Photos of BS-476-6 Fire Propagation Index Test Equipment 

    BS 476-6 Fire Tests on Building Materials and Structures for Fire Propagation

     

     

     

     

    Contact Details
    Advanced Instruments Co.,Ltd

    Contact Person: Mrs. Sandy

    Send your inquiry directly to us (0 / 3000)