Power Supply: | AC220V±10%, 50/60Hz±10% | Display: | LCD |
---|---|---|---|
Keyword: | CT Analyzer,VT Analyzer | Standard: | EC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13 |
Measuring Range: | 0~200V | Current Measurement: | 0~10A |
CT VT Testing Equipment Analyzer
Testing for current transformer equipment:
Testing for Voltage Transformer equipment
Applications of CT/ VT Testing Equipment:
Specifications:
Item Name | CT and VT Testing Equipment | |
Test standards | IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13 | |
Power supply | AC220V±10%, 50/60Hz±10% | |
Voltage output | 0.1~180V (AC) | |
Current output | 0.001~5A(RMS) | |
Power output | 500VA | |
Max. knee voltage measurement | 45KV | |
Current measurement | Range | 0~10A (automatically change range in 0.1/0.4/2/10A) |
Error | <±0.1%+0.01%FS |
Voltage measurement | Range | 0~200V (automatically change range in 1V/10V/70V/200V) | |
Error | < ±0.1%+0.01%FS | ||
Turns ratio measurement Range | 1~35000 1~2000, error<0.05% 2000~5000,error<0.1% 5000~35000,error<0.2% |
||
Phase measurement | error | ±2min | |
resolution | 0.01min | ||
Winding resistance measurement | Range | 0~8kΩ (automatically change range in2ohm/20ohm/80ohm/800ohm/8kohm) | |
Error | < 0.2%RDG+0.02%FS | ||
Maximum resolution : 0.1mΩ | |||
Temperature measurement | -50~100 Celsius degree; error<3 Celsius degree | ||
CT Secondary burden | Range | 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) | |
Error | <0.2%RDG+0.02%FS | ||
Maximum resolution : 0.001ohm | |||
PT Secondary burden |
Error | 0~80kohm (automatically change range in 800ohm/8kohm/80kohm) | |
Maximum | <0.2%RDG+0.02%FS | ||
resolution | 0.1ohm | ||
PT ratio measurement |
Range |
1~35000 1~10000 error<0.1% 10000~35000 error<0.2% |
|
PT ratio error measurement :Typical error<0.05%, Maximum Error<0.1% |
|||
PT phase angle measurement maximum error < 3min | |||
Make evaluation for test results according to selected standards Make word report for test result Make word reports one time for multi-group test records on the PC Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test Compare excitation curves with saved excitation curves in the same window |
|||
Memory capacity | >1000 groups test results | ||
Working condition temperature | -10℃~50℃; moist ≤90% |
Picture of CT VT Analyer