Sales & Support: Request A Quote
Home ProductsElectrical Test Instrument

Automatic Transformer Tangent Delta Power Factor Tester of Electrical Instrument

Automatic Transformer Tangent Delta Power Factor Tester of Electrical Instrument

Automatic Transformer Tangent Delta Power Factor Tester of Electrical Instrument

Product Details:

Place of Origin: China
Brand Name: AI
Certification: ISO
Model Number: TDT

Payment & Shipping Terms:

Minimum Order Quantity: 1 Set
Price: Negotiable
Packaging Details: Carton
Delivery Time: 15 days
Payment Terms: T/T, Western Union, L/C
Supply Ability: 100000 sets per month
Contact Now
Detailed Product Description
Power Supply: AC 220V±10% Display: LCD
Keyword: Tangent Delta Analyzer,Power Factor Tester High Output: 0.5KV~10KV
Maximum Current: 200mA Capacity: 2000VA
Size: 350*270*270mm Weight: 28KG

 

Capacitance Tangent Delta Power Factor Dielectric Loss Tester

 

I.Introduction.

The tangent delta tester is a high-precision instrument, which can be applied to automatically measure electrical loss tangent ( ) and capacitance of all kinds of high voltage electrical equipments on the spot of power plants, substations,laboratory, etc. The instrument is an integrated structure with a dielectric loss test bridge, a variable frequency power supply, a step-up transformer and a SF6 high stability standard capacitor.

 

II.Features:

★Large LCD display

Simple operation, the instrument is equipped with a high-end full touch LCD screen, super touch interface, and each process is very clear. Operators can use it without additional professional training.

★Mass storage data

The instrument is equipped with a calendar chip and large capacity memory. The test results can be stored in chronological order. Users can view historical data at any time and print it out.

★Multiple test modes

The instrument can be tested by high pressure, high voltage, standard, positive connection method, reverse connection method, self excitation method and other methods.

★CVT test step in place

The instrument can also test the full sealed CVT (capacitor voltage transformer) C1, C2 dielectric loss and capacitance, to achieve the C1, C2 simultaneous test.

★Do not dismantle the high-voltage lead measurement CVT

The instrument can accurately measure the dielectric loss and capacitance of CVT without dismantling the CVT high voltage lead.

★CVT reverse shield method for measuring C0

The instrument can be used to measure the dielectric loss and capacitance value of C0 on the upper end of CVT.

★High speed sampling signal

The inverter and sampling circuit of the instrument are all controlled by digital, and the output voltage is adjustable continuously.

★Multi protection security

The instrument has many protection measures, such as input voltage fluctuation, output short circuit, over voltage, over current and temperature.

 

III.Specifications:

1 Use conditions -15℃∽40℃ RH<80%
2 Anti-interference Frequency conversion
3 Power AC 220V±10% Allowable generator
4 High output 0.5KV∽10KV(rated voltage:10KV) Every 0.1kV
0.5KV∽12KV(rated voltage:12KV)
Precision 2%
Maximum current 200mA (rated voltage:10KV)
167mA (rated voltage:12KV)
Capacity 2000VA
5 Self-excited power AC 0V∽50V/15A 45HZ/55HZ 47.5HZ/52.5HZ
55HZ/65HZ 57.5HZ/62.5HZ
Automatic double frequency
6 Resolving power tgδ: 0.001% Cx: 0.001pF
7 Precision △tgδ:±(Reading*1.0%+0.040%)
△C x :±(Reading*1.0%+1.00PF)
8 measuring range tgδ Unlimited
C x 15pF < Cx < 300nF
rated voltage:10KV 10KV Cx < 60 nF
5KV Cx < 150 nF
1KV Cx < 300 nF
rated voltage:12KV 12KV Cx < 30 nF
5KV Cx < 150 nF
1KV Cx < 300 nF
CVT test Cx < 300 nF
9 CVT range 10∽10000
accuracy 0.1%
Resolving power 0.01
10 Exterior dimension 350(L)×270(W)×270(H)
11 Memory size The 200 groups supports U disk data storage
12 Weight 28 Kg

Contact Details
Advanced Instruments Co.,Ltd

Contact Person: Mrs. Sandy

Send your inquiry directly to us (0 / 3000)